An intermittent energy source is any source of energy that is not continuously available due to some factor outside direct control. The intermittent source may be quite predictable, for example, tidal power, but cannot be dispatched to meet the demand of a power system. Effective use of intermittent sources in an electric power grid usually relies on using the intermittent sources to displace fuel that would otherwise be consumed by non-renewable power stations, or by storing energy in the form of renewable pumped storage, compressed air or ice, for use when needed, or as electrode heating for district heating schemes.
The storage of energy to fill the shortfall intermittency or for emergencies is part of a reliable energy supply. The capacity of a reliable renewable energy supply, can additionally be fulfilled by the use of latency measures and backup or extra infrastructure and technology, using mixed renewables to produce electricity above the intermittent average, which may be utilised to meet regular and unanticipated supply demands.[1]
The penetration of intermittent renewables in most power grids is low, but wind generates circa 16% (EWEA - 2011 European Statistics, February 2012) of electric energy in Spain and Portugal,[2] 9% in Ireland,[2] and 7% in Germany.[3] Wind provides nearly 20% of the electricity generated in Denmark;[4][5] to operate with this level of penetration, Denmark exports surpluses and imports during shortfalls to and from the EU grid, particularly Norwegian Hydro, to balance supply with demand.[6] It also uses[citation needed] large numbers of combined heat and power (CHP) stations which can rapidly adjust output. The large thermal stores in these systems are also utilised to store surplus wind energy,[citation needed] since thermal storage is the cheapest form of energy storage.
The use of small amounts of intermittent power has little effect on grid operations. Using larger amounts of intermittent power may require upgrades or even a redesign of the grid infrastructure.[7][8]
Several key terms are useful for understanding the issue of intermittent power sources. These terms are not standardized, and variations may be used. Most of these terms also apply to traditional power plants.
Intermittency inherently affects solar energy, as the production of electricity from solar sources depends on the amount of light energy in a given location. Solar output varies throughout the day and through the seasons, and is affected by cloud cover. These factors are fairly predictable, and some solar thermal systems make use of heat storage to produce power when the sun is not shining.
The extent to which the intermittency of solar-generated electricity is an issue will depend to some extent on the degree to which the generation profile of solar corresponds to demand. For example, solar thermal power plants such as Nevada Solar One are somewhat matched to summer peak loads in areas with significant cooling demands, such as the south-western United States. Thermal energy storage systems can improve the degree of match between supply and consumption. The increase in capacity factor of thermal systems does not represent an increase in efficiency, but rather a spreading out of the time over which the system generates power.[16][17][18]
Wind-generated power is a variable resource, and the amount of electricity produced at any given point in time by a given plant will depend on wind speeds, air density, and turbine characteristics (among other factors). If wind speed is too low (less than about 2.5 m/s) then the wind turbines will not be able to make electricity, and if it is too high (more than about 25 m/s) the turbines will have to be shut down to avoid damage. While the output from a single turbine can vary greatly and rapidly as local wind speeds vary, as more turbines are connected over larger and larger areas the average power output becomes less variable.[19]
According to a study of wind in the United States, ten or more widely separated wind farms connected through the grid could be relied upon for from 33 to 47% of their average output (15–20% of nominal capacity) as reliable, baseload power, as long as minimum criteria are met for wind speed and turbine height.[27][28] When calculating the generating capacity available to meet summer peak demand, ERCOT (manages Texas grid) counts wind generation at 8.7% of nameplate capacity.[29]
In five U.S. states, 10 percent or more of electricity generation came from wind power in 2011. South Dakota leads the states, with wind power making up 22 percent of its electricity generation in 2011. Iowa generated 19 percent of its electricity in 2011 with wind energy. And in North Dakota, wind power’s contribution was 15 percent.[30]
Wind generates about 16% (EWEA - 2011 European Statistics, February 2012) of electric energy in Spain and Portugal,[2] 9% in Ireland,[2] and 7% in Germany.[3] Wind provides nearly 20% of the electricity generated in Denmark,[4][31] to meet this percentage Denmark exports surpluses and imports during shortfalls to and from the EU grid, particularly Norwegien Hydro, to balance supply with demand.[6] It also uses large numbers of Combined Heat And power stations which can rapidly flex output. The large thermal stores in these systems are also utilised to store surplus wind energy, since thermal storage is the cheapest form of energy storage.
Because wind power is generated by large numbers of small generators, individual failures do not have large impacts on power grids. This feature of wind has been referred to as resiliency.[32]
Wind power is affected by air temperature because colder air is more dense and therefore more effective at producing wind power. As a result, wind power is affected seasonally (more output in winter than summer) and by daily temperature variations. During the 2006 California heat storm output from wind power in California significantly decreased to an average of 4% of capacity for 7 days.[33] A similar result was seen during the 2003 European heat wave, when the output of wind power in France, Germany, and Spain fell below 10% during peak demand times.[34]
According to an article in EnergyPulse, "the development and expansion of well-functioning day-ahead and real time markets will provide an effective means of dealing with the variability of wind generation."[35]
The combination of diversifying variable renewables by type and location, forecasting their variation, and integrating them with despatchable renewables, flexible fueled generators, and demand response can create a power system that has the potential to meet our needs reliably. Integrating ever-higher levels of renewables is being successfully demonstrated in the real world:[36]
In 2009, eight American and three European authorities, writing in the leading electrical engineers' professional journal, didn't find "a credible and firm technical limit to the amount of wind energy that can be accommodated by electricity grids". In Fact, not one of more than 200 international studies, nor official studies for the eastern and western U.S. regions, nor the International Energy Agency, has found major costs or technical barriers to reliably integrating up to 30% variable renewable supplies into the grid, and in some studies much more.[36]
Mark Z. Jacobson has studied how wind, water and solar technologies can be integrated to provide the majority of the world's energy needs.[37] He advocates a "smart mix" of renewable energy sources to reliably meet electricity demand:
Because the wind blows during stormy conditions when the sun does not shine and the sun often shines on calm days with little wind, combining wind and solar can go a long way toward meeting demand, especially when geothermal provides a steady base and hydroelectric can be called on to fill in the gaps.[38]
Mark A. Delucchi and Mark Z. Jacobson argue that there are at least seven ways to design and operate renewable energy systems so that they will reliably satisfy electricity demand:[39]
Technological solutions to mitigate large-scale wind energy type intermittency exist such as increased interconnection (the European super grid), Demand response, load management, diesel generators (in the British National Grid, Frequency Response / National Grid Reserve Service type schemes, and use of existing power stations on standby. Studies by academics and grid operators indicate that the cost of compensating for intermittency is expected to be high at levels of penetration above the low levels currently in use today[40][41][42] Large, distributed power grids are better able to deal with high levels of penetration than small, isolated grids. For a hypothetical European-wide power grid, analysis has shown that wind energy penetration levels as high as 70% are viable,[43] and that the cost of the extra transmission lines would be only around 10% of the turbine cost, yielding power at around present day prices.[44] Smaller grids may be less tolerant to high levels of penetration.[7][45]
Matching power demand to supply is not a problem specific to intermittent power sources. Existing power grids already contain elements of uncertainty including sudden and large changes in demand and unforeseen power plant failures. Though power grids are already designed to have some capacity in excess of projected peak demand to deal with these problems, significant upgrades may be required to accommodate large amounts of intermittent power. The International Energy Agency (IEA) states: "In the case of wind power, operational reserve is the additional generating reserve needed to ensure that differences between forecast and actual volumes of generation and demand can be met. Again, it has to be noted that already significant amounts of this reserve are operating on the grid due to the general safety and quality demands of the grid. Wind imposes additional demands only inasmuch as it increases variability and unpredictability. However, these factors are nothing completely new to system operators. By adding another variable, wind power changes the degree of uncertainty, but not the kind..."[19]
A November 2006 analysis found that "wind power may be able to cover more than 50% of the Danish electricity consumption in 2025" under conditions of high oil prices and higher costs for CO2 allowances.[46] Denmark's two grids (covering West Denmark and East Denmark separately) each incorporate high-capacity interconnectors to neighbouring grids where some of the variations from wind are absorbed.[47]
Many commentators[who?] concentrate on whether or not wind has any "capacity credit" without defining what they mean by this and its relevance. Wind does have a capacity credit, using a widely accepted and meaningful definition, equal to about 20% of its rated output (but this figure varies depending on actual circumstances). This means that reserve capacity on a system equal in MW to 20% of added wind could be retired when such wind is added without affecting system security or robustness.
UK academic commentator Graham Sinden, of Oxford University, argues that this issue of capacity credit is a "red herring" in that the value of wind generation is largely due to the value of displaced fuel, not any perceived capacity credit – it being well understood by the wind energy proponents that conventional capacity will be retained to "fill in" during periods of low or no wind.[48] The main value of wind, (in the UK, 5 times the capacity credit value[49]) is its fuel and CO2 savings. Wind does not require any extra back-up, as is often wrongly claimed, since it uses the existing power stations, which are already built, as back-up, and which are started up during low wind periods, just as they are started up now, during the non availability of other conventional plant. More spinning reserve, of existing plant, is required, but this again is already built[citation needed] and has a low cost comparatively.[50][51]
Hydroelectric power is usually extremely dispatchable and more reliable than other renewable energy sources. Many dams can provide hundreds of megawatts within seconds of demand (see Ffestiniog power station). The exact nature of the power availability depends on the type of plant.
In run-of-the-river hydroelectricity, power availability is highly dependent on the flow of the river, making this type of generation mostly suitable only at locations where flow levels are controlled by upstream dams.[19]
In conventional hydroelectric plants, there is a reservoir and a one-way generator. The water flow through its turbines can be adjusted frequently to meet changing demand throughout the day by running the generator when demand is high and not running it when demand is low.
Pumped-storage hydroelectricity can make an even more significant contribution to peaking ability of the grid. These just move water between reservoirs and are powered by power from the grid when demand is low and put power back into the grid when demand is high. There also exist combined pump-storage plants that use river flow as well as extra pumping when demand is low, such as the 240 MW Lewiston Pump-Generating Plant.[19]
Direct pumped-storage does not contribute any net generation to the grid, in fact, it increases the fuel used by other power plants because there is inefficiency in the turbine/generator. The economic benefit of pumped-storage plants lies only in increasing the capacity of the grid. This type of plant works well on a grid with many nuclear or renewable energy plants because the fuel is very cheap or essentially free, so it costs very little to keep them running at high power during the night when demand is low. Both pump-storage plants and natural flow hydro plants can help allow for intermittency of other plants by running at higher capacity for short times, but assistance is limited by the total capacity of the hydroelectric plant.
Once a conventional power station has come offline it may stay that way for more than a week.[52]
Conventional power plants (as well as nuclear plants) use water for cooling, and water shortages during hot summer months have occasionally resulted in periods when output has had to be curtailed, notably in France in 2006.[53]
Conventional power plant failures can remove large amounts of capacity from the grid suddenly, resulting in blackouts.[54]
Gas-fired plants are typically very reliable and dispatchable. These kinds of plants also often have the ability to quickly vary their output to adjust to the frequent jumps and changes in consumer demand. Thus these are very good as peaking units. These benefits are weighted against the cost of the gas fuel when deployed in the grid.[55]
Nuclear power is considered a base load power source, in that its output is nearly constant and other types of plants are adjusted with changes in demand. This is done because output changes can only be made in small increments, and because of small fuel costs - there is little marginal cost between running at a low power and a high power, therefore it is cheapest for the system to run the nuclear plants at high power.
Every year or two (depending on the plant), the plant must be shut down for planned outages for about a month. This is typically done in the spring or autumn (fall) when electricity demand is lower, as such, on a national scale power output from nuclear increases corresponding with demand during the peak summer and winter months. This change in output commonly occurs on a yearly basis.
It is rare that nuclear power plants adjust their power output to correspond with demand on a daily basis because pressurized water reactors (PWR, which are the vast majority of nuclear power plants) use a chemical shim in the moderator–coolant to control their power level. (Boiling water reactors (BWR), however, can use a combination of control rods and recirculation water flow speed to control their power level, and so in markets such as Chicago, Illinois where half of the local utility's fleet is BWRs it is common to load-follow although less economic to do so.)
In the UK one of the key criteria for determining the amount of required spinning reserve is the possible loss of Sizewell B, a 1.2 GW nuclear power plant.[57] At one point in the fall of 2007, out of 16 nuclear power stations in the UK, seven were offline due to a combination of planned and unplanned outages.[58]
Small high-speed diesels are very commonly used within large power grids throughout North America and Europe. France uses about 5 GW of such diesels to cover the intermittency of their nuclear stations; these are all in private hands - at small scales factories and the like - with their usage being triggered semi-randomly by a special tariff - EJP[59]- which encourages these users to start their diesels.
In USA and UK these diesels have usually been purchased for other reasons e.g. for emergency standby, in water works, hotels, hospitals, etc. and in some cases for electricity substations - e.g. Cuyahoga Falls, USA (10 × 1.6 MW Caterpillar) and Tregarron Mid Wales UK (3 × 1.6 MW Caterpillar), but can be readily used to automatically synchronize and feed into the grid.
In the UK 500 MW of such plant is routinely started within a few minutes; this is perfectly acceptable to the engines' service life in a scheme operated by National Grid called National Grid Reserve Service. It has been established that there is 20 GW of such diesel plant in the UK and it has been pointed out that there is no technical reason why this quantity could not be brought into the Reserve Service scheme to assist handling very rapid changes in renewable output, whilst conventional plant is started or indeed stopped.[48][60] [61]
All sources of electrical power have some degree of unpredictability, and demand patterns routinely drive large swings in the amount of electricity that suppliers feed into the grid. Wherever possible, grid operations procedures are designed to match supply with demand at high levels of reliability, and the tools to influence supply and demand are well-developed. The introduction of large amounts of highly variable power generation may require changes to existing procedures and additional investments.
All managed grids already have existing operational and "spinning" reserve to compensate for existing uncertainties in the power grid. The addition of intermittent resources such as wind does not require 100% "back-up" because operating reserves and balancing requirements are calculated on a system-wide basis, and not dedicated to a specific generating plant.
At times of low or falling demand where wind output may be high or increasing, grid stability may require lowering the output of various generating sources or even increasing demand, possibly by using energy storage to time-shift output to times of higher demand. Such mechanisms can include:
Storage of electrical energy results in some lost energy because storage and retrieval are not perfectly efficient. Storage may also require substantial capital investment and space for storage facilities.
The variability of production from a single wind turbine can be high. Combining any additional number of turbines (for example, in a wind farm) results in lower statistical variation, as long as the correlation between the output of each turbine is imperfect, and the correlations are always imperfect due to the distance between each turbine. Similarly, geographically distant wind turbines or wind farms have lower correlations, reducing overall variability. Since wind power is dependent on weather systems, there is a limit to the benefit of this geographic diversity for any power system.
Multiple wind farms spread over a wide geographic area and gridded together produce power more constantly and with less variability than smaller installations. Wind output can be predicted with some degree of confidence using weather forecasts, especially from large numbers of turbines/farms. The ability to predict wind output is expected to increase over time as data is collected, especially from newer facilities.
Penetration refers to the proportion of a power source on a system, expressed as a percentage.[12] There are several ways that this can be calculated, with the different methods yielding different penetrations. It can be calculated either as:[72]
The level of penetration of intermittent variable sources is significant for the following reasons:
Renewable electricity supply in the 20-50+% penetration range has already been implemented in several European systems, albeit in the context of an integrated European grid system:[36]
In 2010, four German states, totaling 10 million people, relied on wind power for 43-52% of their annual electricity needs. Denmark isn't far behind, supplying 22% of its power from wind in 2010 (26% in an average wind year). The Extremadura region of Spain is getting up to 25% of its electricity from solar, while the whole country meets 16% of its demand from wind. Just during 2005-2010, Portugal vaulted from 17% to 45% renewable electricity.[36]
There is no generally accepted maximum level of penetration, as each system's capacity to compensate for intermittency differs, and the systems themselves will change over time. Discussion of acceptable or unacceptable penetration figures should be treated and used with caution, as the relevance or significance will be highly dependent on local factors, grid structure and management, and existing generation capacity.
For most systems worldwide, existing penetration levels are significantly lower than practical or theoretical maximums; for example, a UK study found that "it is clear that intermittent generation need not compromise electricity system reliability at any level of penetration foreseeable in Britain over the next 20 years, although it may increase costs."[72]
There is no generally accepted maximum penetration of wind energy that would be feasible in any given grid. Rather, economic efficiency and cost considerations are more likely to dominate as critical factors; technical solutions may allow higher penetration levels to be considered in future, particularly if cost considerations are secondary.
High penetration scenarios may be feasible in certain circumstances:
Studies have been conducted to assess the viability of specific penetration levels in specific energy markets.
A series of detailed modelling studies by Dr. Gregor Czisch, which looked at the European wide adoption of renewable energy and interlinking power grids the European super grid using HVDC cables, indicates that the entire European power usage could come from renewables, with 70% total energy from wind at the same sort of costs or lower than at present.[45] This proposed large European power grid has been called a "super grid."[75][76]
The model deals with intermittent power issues by using base-load renewables such as hydroelectric and biomass for a substantial portion of the remaining 30% and by heavy use of HVDC to shift power from windy areas to non-windy areas. The report states that "electricity transport proves to be one of the keys to an economical electricity supply" and underscores the importance of "international co-operation in the field of renewable energy use [and] transmission."[45][77][78]
Dr. Czisch described the concept in an interview, saying "For example, if we look at wind energy in Europe. We have a winter wind region where the maximum production is in winter and in the Sahara region in northern Africa the highest wind production is in the summer and if you combine both, you come quite close to the needs of the people living in the whole area - let's say from northern Russia down to the southern part of the Sahara."[79]
A study of the grid in Ireland indicates that it would be feasible to accommodate 42% (of demand) renewables in the electricity mix.[80] This acceptable level of renewable penetration was found in what the study called Scenario 5, provided 47% of electrical capacity (different from demand) with the following mix of renewable energies:
The study cautions that various assumptions were made that "may have understated dispatch restrictions, resulting in an underestimation of operational costs, required wind curtailment, and CO2 emissions" and that "The limitations of the study may overstate the technical feasibility of the portfolios analyzed..."
Scenario 6, which proposed renewables providing 59% of electrical capacity and 54% of demand had problems. Scenario 6 proposed the following mix of renewable energies:
The study found that for Scenario 6, "a significant number of hours characterized by extreme system situations occurred where load and reserve requirements could not be met. The results of the network study indicated that for such extreme renewable penetration scenarios, a system re-design is required, rather than a reinforcement exercise." The study declined to analyze the cost effectiveness of the required changes because "determination of costs and benefits had become extremely dependent on the assumptions made" and this uncertainty would have impacted the robustness of the results.[7]
A study published in October 2006, by the Ontario Independent Electric System Operator (IESO) found that "there would be minimal system operation impacts for levels of wind capacity up to 5,000 MW," which corresponds to a peak penetration of 17%[81]
Estimates of the cost of wind energy may include estimates of the "external" costs of wind variability, or be limited to the cost of production. All electrical plant has costs that are separate from the cost of production, including, for example, the cost of any necessary transmission capacity or reserve capacity in case of loss of generating capacity. Many types of generation, particularly fossil fuel derived, will also have cost externalities such as pollution, greenhouse gas emission, and habitat destruction which are generally not directly accounted for. The magnitude of the economic impacts is debated and will vary by location, but is expected to rise with higher penetration levels. At low penetration levels, costs such as operating reserve and balancing costs are believed to be insignificant.
Intermittency may introduce additional costs that are distinct from or of a different magnitude than for traditional generation types. These may include:
Studies have been performed to determine the costs of variability. RenewableUK states:
| “ | A review of integration studies, worldwide, suggests that the additional costs of integrating wind are around £2/MWh with 10% wind, rising to £3/MWh with 20% wind.[57] | ” |
An official at Xcel Energy claimed that at 20 percent penetration, additional standby generators to compensate for wind in Colorado would cost $8 per MWh, adding between 13% and 16% to the $50–$60 cost per MWh of wind energy.[84]
The Union of Concerned Scientists conducted a study of the costs to increase the renewable penetration in Colorado to 10% and found that for an average residential bill "customers of municipal utilities and rural electric cooperatives that opt out of the solar energy requirement" would save 4 cents per month, but that for Xcel Energy customers there would be additional cost of about 10 cents per month. Total impact on all consumers would be $4.5 million or 0.01% over two decades.[85][86]
A detailed study for UK National Grid (a private power company) states "We have estimated that for the case with 8,000 MW of wind needed to meet the 10% renewables target for 2010, balancing costs can be expected to increase by around £2 per MWh of wind production. This would represent an additional £40million per annum, just over 10% of existing annual balancing costs."[87][88]
In evidence to the UK House of Lords Economic Affairs Select Committee, National Grid have quoted estimates of balancing costs for 40% wind and these lie in the range £500-1000M per annum. "These balancing costs represent an additional £6 to £12 per annum on average consumer electricity bill of around £390."[89]
National Grid notes that "increasing levels of such renewable generation on the system would increase the costs of balancing the system and managing system frequency."[88]
A 2003 report by Carbon Trust and the UK Department of Trade and Industry (DTI) found that the costs for reinforcement and new build of transmission and distribution systems to support 10% renewable electricity in the UK by 2010 would be £1.6 to £2.4 billion. The study classified "Intermittency" as "Not a significant issue" for the 2010 target.[8] The same 2003 study found that achieving 20% renewable electricity in the UK by 2020 would cost £3.2bn to £4.5bn in transmission and distribution system construction and reinforcement. The study classified "Intermittency" as a "Significant Issue" for the 2020 target.[8]
Minnesota study on wind penetration levels and found that "total integration operating cost for up to 25% wind energy" would be less than $0.0045 per kWh (additional).[90][91]
There are differing views about some sources of renewable energy and intermittency. The World Nuclear Association argues that the sun, wind, tides and waves cannot be controlled to provide directly either continuous base-load power, or peak-load power when it is needed.[92] Proponents of renewable energy use argue that the issue of intermittency of renewables is over-stated, and that practical experience demonstrates this.[93] In any case, geothermal renewable energy has no intermittency.
The World Nuclear Association states that:
"Obviously sun, wind, tides and waves cannot be controlled to provide directly either continuous base-load power, or peak-load power when it is needed,..." "In practical terms non-hydro renewables are therefore able to supply up to some 15–20% of the capacity of an electricity grid, though they cannot directly be applied as economic substitutes for most coal or nuclear power, however significant they become in particular areas with favourable conditions." "If the fundamental opportunity of these renewables is their abundance and relatively widespread occurrence, the fundamental challenge, especially for electricity supply, is applying them to meet demand given their variable and diffuse nature. This means either that there must be reliable duplicate sources of electricity beyond the normal system reserve, or some means of electricity storage." "Relatively few places have scope for pumped storage dams close to where the power is needed, and overall efficiency is less than 80%. Means of storing large amounts of electricity as such in giant batteries or by other means have not been developed."[94]
On December 10, 2007 Patrick Moore, co-chair of the Clean & Safe Energy Coalition[95] - a pro-nuclear group funded by the Nuclear Energy Institute[96] - wrote:
| “ | Greenpeace is deliberately misleading the public into thinking that wind and solar energy, both of which are inherently intermittent and unreliable, can replace baseload power that is continuous and reliable. Only three technologies can produce large amounts of baseload power: fossil fuels, hydroelectric plants and nuclear power. Given that we want to reduce fossil fuels and that potential hydroelectric sites are becoming scarce, nuclear power is the main option... Over the past 10 years, Germany and Denmark have poured billions of taxpayers' euros into wind and solar energy in the vain hope that this would allow them to shut down fossil fuel and nuclear plants. They have not succeeded because every solar panel and every wind turbine must be backed up by reliable power when the sun isn't shining and the wind isn't blowing.[97] | ” |
Mr. Moore is a co-founder and former leader of Greenpeace, but he has not been involved with Greenpeace since 1986.[98]
The US Federal Energy Regulatory Commission (FERC) Chairman Jon Wellinghoff has stated that "baseload capacity is going to become an anachronism" and that no new nuclear or coal plants may ever be needed in the United States.[99][100] This however is a minority viewpoint within President Obama's administration[101] which via expanded federal loan guarantees in the proposed 2011 budget is supporting a nuclear renaissance.[102]
Australian researchers at the University of New South Wales claim to have solved the energy storage problem for solar and wind power with the development of vanadium redox batteries. (U.S. patent issued in 1986).
Some renewable electricity sources have identical variability to coal-fired power stations, so they are base-load, and can be integrated into the electricity supply system without any additional back-up. Examples include:
Furthermore, supporters argue that the total electricity generated from a large-scale array of dispersed wind farms, located in different wind regimes, cannot be accurately described as intermittent, because it does not start up or switch off instantaneously at irregular intervals.[104] With a small amount of supplementary peak-load plant, which operates infrequently, large-scale distributed wind power can substitute for some base-load power and be equally reliable.[105]
Hydropower can be intermittent and/or dispatchable, depending on the configuration of the plant. Typical hydroelectric plants in the dam configuration may have substantial storage capacity, and be considered dispatchable. Run of the river hydroelectric generation will typically have limited or no storage capacity, and will be variable on a seasonal or annual basis (dependent on rainfall and snow melt).[19]
Amory Lovins suggests a few basic strategies to deal with these issues:
| “ | "The variability of sun, wind and so on, turns out to be a non-problem if you do several sensible things. One is to diversify your renewables by technology, so that weather conditions bad for one kind are good for another. Second, you diversify by site so they're not all subject to the same weather pattern at the same time because they're in the same place. Third, you use standard weather forecasting techniques to forecast wind, sun and rain, and of course hydro operators do this right now. Fourth, you integrate all your resources — supply side and demand side..."[106] | ” |
Moreover, efficient energy use and energy conservation measures can reliably reduce demand for base-load and peak-load electricity.[20][103]
Several studies have demonstrated the technical feasibility of integrating intermittent power at levels substantially higher than is common in most countries (from 15-30% penetration),[citation needed] and at least three countries have more than 20% wind penetration.[citation needed] Relatively few changes to large grids are normally required and the associated system costs are moderate.[citation needed] International groups are studying much higher penetrations (30-75%, corresponding to up to 20% of national electricity consumption) and preliminary conclusions are that these levels are also technically feasible.[107] In the UK, one summary of other studies indicated that if assuming that wind power contributed less than 20% of UK power consumption, then the intermittency would cause only moderate cost.[108]
Methods to manage wind power integration range from those that are commonly used at present (e.g. demand management) to potential new technologies for grid energy storage. Improved forecasting can also contribute as the daily and seasonal variations in wind and solar sources are to some extent predictable.
The Pembina Institute and the World Wide Fund for Nature state in the Renewable is Doable plan that resilience is a feature of renewable energy:
| “ | Diversity and dispersal also add system security. If one wind turbine fails, the lights won't flicker. If an entire windfarm gets knocked out by a storm, only 40,000 people will lose power. If a single Darlington reactor goes down, 400,000 homes, or key industries, could face instant blackouts. To hedge this extra risk, high premiums have to be paid for decades to ensure large blocks of standby generation.[32] | ” |